PC-S200

PC-S200 Soundproof Canopy Generating Set

A 200 kVA canopy set for outdoor installation beside an occupied building, attenuated on both intake and discharge.

  • Attenuated intake and discharge with a lined internal exhaust silencer inside the canopy
  • Canopy sheet rated IP44 with lockable access doors on both long faces
  • 400 L bunded tank integrated into the baseframe, no separate bund required
  • Emergency stop mushroom head on the outside of the canopy, reachable without opening a door
Talk to an engineer

Specifications

Standby rating (ESP)
200 kVA / 160 kW
Prime rating (PRP)
182 kVA / 146 kW
Voltage / frequency
400 / 230 V, 3-phase, 50 Hz
Engine
6-cylinder in-line, 6.7 L, turbocharged diesel
Alternator
Brushless, AVR regulated, Class H, IP23
Fuel at 75% load
31.2 L/h
Sound pressure at 7 m
66 dB(A)
Dimensions / dry weight
3900 x 1300 x 2100 mm / 2760 kg

Product detail

A canopy set is bought for one number: the sound pressure at the boundary. The PC-S200 is measured at 66 dB(A) at 7 m in free field, which is the figure that goes into an acoustic assessment. It is not the figure you will see on site if the set is installed in a corner formed by two hard walls, and the general arrangement drawing states that plainly so the assessment is done on the real geometry.

How the attenuation works

Air enters through a lined intake plenum, crosses the alternator and engine, and leaves through a lined discharge plenum. The exhaust silencer sits inside the canopy rather than on the roof, so the tail pipe is the only hot surface outside. Restricting airflow is the usual cause of a canopy set running hot, so the plenum free area is fixed by design and is not adjustable in the field.

Enclosure

Sheet steel, powder coated, with lockable doors on both long faces for access to the control panel, the filters and the battery. The tank is integrated into the baseframe and bunded to the full tank volume, so the set can stand on a plain concrete pad.

Fuel

The 400 L integrated tank gives roughly 12 hours at 75 per cent of prime rating. Where a longer autonomy is required, the set accepts a bulk tank feed through a float-switch day tank arrangement.

Enquire about this model

PC-S200 Soundproof Canopy Generating Set

Send the connected load, the starting profile and the duty class, and we will confirm the rating, the build and the shipping option.

Include the load schedule and the site conditions. The reply comes from the engineer who sizes the set.