Immersion Cooling
KX-IMMERSE T200
Single-Phase Immersion Tank
A 200 kW dielectric bath with an integrated coolant-to-water exchanger and 100 % heat capture — no server fans at all.
- Rated capacity
- 200 kW
- Per rack
- 200 kW
- Nominal Delta-T
- 12 K
- Nominal flow
- 239 L/min
- Supply water
- W25 – W45 (25 – 45 °C)
- Max pressure
- 3.0 bar
- Partial PUE
- 1.04
- Working fluid
- Single-phase synthetic dielectric
Immersion is the end of the density argument. Submerge the board and there is no air path left to optimise, no fan to fail, and no thermal interface material to argue about.
Every watt to fluid
Direct-to-chip captures 75 to 95 % of rack heat and leaves the rest — memory, drives, VRMs, network — for the air system to collect. The T200 captures all of it. That last fifteen percent is exactly the part that forces you to keep a CRAH plant running, which is why the partial PUE lands at 1.04 rather than 1.08.
The fans that stop existing
Server fans consume 8 to 15 % of IT power in a dense air-cooled rack. In the T200 there are none, so that power is not spent and its heat is not generated. It is the rare efficiency measure that improves two terms of the equation at once.
What changes operationally
We are direct about this: immersion changes how your team works. Boards come out wet and drip into a tray on a gantry. Some components need qualification for fluid compatibility. Sites that succeed with immersion decide to change procedure deliberately; sites that treat it as a drop-in are the ones that struggle.
Warm water, no chiller
At 45 °C facility water the T200 still holds junction temperatures comfortably. At that supply a dry cooler covers the year in almost any climate and the chiller becomes a redundancy asset rather than an operating cost.
Technical data
Full specification
Values are at nominal duty. Ask us for the full performance map if you are working outside these conditions.
| Rated capacity | 200 kW |
|---|---|
| Configuration | Single-phase, open bath |
| Facility water temperature | 25 – 45 °C |
| Nominal Delta-T | 12 K |
| Water-side flow rate | 239 L/min |
| Dielectric volume | 760 L |
| Heat capture ratio | 100 % |
| Maximum working pressure | 3 bar |
| Node capacity | 24 × 2U equivalent |
| Fluid type | Synthetic single-phase dielectric |
| Dimensions (L × W × H) | 2,400 × 1,200 × 1,100 mm |
| Mass (filled) | 1,640 kg |
| Partial PUE contribution | 1.04 |
Module 05 — Flow envelope
Delta-T against required flow
This unit rejects 200 kW. Widening the temperature difference across the loop cuts the volume of water you have to move — and pump power falls with roughly the cube of flow.
- Required flow
- 239 L/min
- Return temperature
- 42.0 °C at W30 supply
- Relative pump power
- 100 % of nominal
Water at 4.18 kJ/kg·K, density taken as 1 kg/L. Pump power index scales with the cube of the flow ratio against this unit’s nominal 12.0 K design point.