Immersion Cooling

KX-IMMERSE T200

Single-Phase Immersion Tank

A 200 kW dielectric bath with an integrated coolant-to-water exchanger and 100 % heat capture — no server fans at all.

Rated capacity
200 kW
Per rack
200 kW
Nominal Delta-T
12 K
Nominal flow
239 L/min
Supply water
W25 – W45 (25 – 45 °C)
Max pressure
3.0 bar
Partial PUE
1.04
Working fluid
Single-phase synthetic dielectric
Full specifications
Single-phase immersion cooling tank filled with clear dielectric fluid and server boards submerged vertically in rows

Immersion is the end of the density argument. Submerge the board and there is no air path left to optimise, no fan to fail, and no thermal interface material to argue about.

Every watt to fluid

Direct-to-chip captures 75 to 95 % of rack heat and leaves the rest — memory, drives, VRMs, network — for the air system to collect. The T200 captures all of it. That last fifteen percent is exactly the part that forces you to keep a CRAH plant running, which is why the partial PUE lands at 1.04 rather than 1.08.

The fans that stop existing

Server fans consume 8 to 15 % of IT power in a dense air-cooled rack. In the T200 there are none, so that power is not spent and its heat is not generated. It is the rare efficiency measure that improves two terms of the equation at once.

What changes operationally

We are direct about this: immersion changes how your team works. Boards come out wet and drip into a tray on a gantry. Some components need qualification for fluid compatibility. Sites that succeed with immersion decide to change procedure deliberately; sites that treat it as a drop-in are the ones that struggle.

Warm water, no chiller

At 45 °C facility water the T200 still holds junction temperatures comfortably. At that supply a dry cooler covers the year in almost any climate and the chiller becomes a redundancy asset rather than an operating cost.

Technical data

Full specification

Values are at nominal duty. Ask us for the full performance map if you are working outside these conditions.

Technical specifications
Rated capacity 200 kW
Configuration Single-phase, open bath
Facility water temperature 25 – 45 °C
Nominal Delta-T 12 K
Water-side flow rate 239 L/min
Dielectric volume 760 L
Heat capture ratio 100 %
Maximum working pressure 3 bar
Node capacity 24 × 2U equivalent
Fluid type Synthetic single-phase dielectric
Dimensions (L × W × H) 2,400 × 1,200 × 1,100 mm
Mass (filled) 1,640 kg
Partial PUE contribution 1.04

Module 05 — Flow envelope

Delta-T against required flow

This unit rejects 200 kW. Widening the temperature difference across the loop cuts the volume of water you have to move — and pump power falls with roughly the cube of flow.

0 188 375 563 750 4 K 8 K 12 K 16 K 20 K Flow — L/min Loop Delta-T
Required flow
239 L/min
Return temperature
42.0 °C at W30 supply
Relative pump power
100 % of nominal

Water at 4.18 kJ/kg·K, density taken as 1 kg/L. Pump power index scales with the cube of the flow ratio against this unit’s nominal 12.0 K design point.